Causes and Solutions of Air Source Heat Pump Frost
2020/07/23
During the operation of the air source heat pump in winter, when the air passes through the outdoor heat exchanger coil, water will condense on the surface of the coil, and then form ice or frost. The ice or frost on the coil will not only reduce heat exchange area, and will reduce the air volume that can pass. With the continuous increase of frost, it will affect the heat exchange effect between the air and the coil. Therefore, defrost is a unique phenomenon of air source heat pumps in winter.

Heat pump air-conditioning unit uses the following methods to determine whether to defrost: If the relationship between outdoor unit coil temperature and the outdoor air temperature meets the relevant conditions for 5 minutes, the defrost cycle will be performed, which is determined by the setting value of the defrost temperature switch.
There is a wrong concept that must be corrected, that is, it is not that the lower the outdoor temperature, the more defrosting times. Sometimes the situation is just the opposite. In sunny weather, the number of defrosts in a day is relatively small, about 8 hours once, and about three times a day. In rainy and snowy weather, there are more defrosts in a day, about 2~3 hours once. The worst conditions are in rainy and snowy weather between 0~5 ℃, sometimes even once every 1~1.5h.

It can be seen that the time interval of defrosting is mainly determined by the relative humidity of outdoor air. The higher the relative humidity of outdoor air, the more defrosting times, and vice versa. In addition to normal defrosting, there is also a situation where the machine defrosts malfunctions. So when the machine cannot defrost normally, what should be done?
1. What should we do if the evaporator freezes locally?
The cause of the evaporator freezing may be because there is no frost at the defrost sensor and the defrost point is not accurate. The solution is to manually force defrost and move the defrost sensor to the frosted place.
2. What should we do if the evaporator does not defrost?
There are three possibilities. One is that the defrost sensor and the ambient temperature sensor are faulty and need to be replaced; the other is the lack of fluorine or the system is blocked, and the system needs to be fluorinated according to the standard, need to clean the system; the third is that the four-way valve does not change direction , need check if the valve is energized and operating normally.
3. What should we do if the defrosting is not clean?
The problem may be that the temperature setting of the exit defrosting coil is too low, resulting in unclean defrosting. At this time, you need to adjust the defrosting parameters and observe patiently until the defrosting is over. It may also be that the sensor probe is not placed in the most severely frosted place, so just move the probe.
4. What should we do if all the fins are frosted?
It may be because the temperature of the entering defrosting coil is set too low, or the defrosting time interval is set too long, and the defrosting action cannot be entered in time. Need to adjust the defrosting parameters, increase the temperature of entering the defrosting coil, and shorten the defrosting time interval.
5. How to deal with frequent frost in a short time?
The fin heat exchanger is blocked, the fan motor is damaged, or the fan air volume configuration is too small. The solution is to clean the heat exchanger, repair and replace the motor.