The Role And Characteristics Of Evaporator In Refrigeration System

2020/07/16

The four major components of the refrigeration system are the compressor, evaporator, condenser and throttling device. The role of the evaporator is to evaporate (boiling) the refrigerant and absorb the heat of the refrigerant to achieve the purpose of refrigeration. There are many types of evaporator, we will mainly introduce the working principle and structural characteristics of several common evaporators as following:

 

1.Dry type evaporator

The refrigerant passes inside the heat exchange tube and water flows in the shell outside heat exchange tube. The heat transfer efficiency of this type of heat exchanger is relatively low. Its advantages: it is easy to return oil, and the control is relatively simple, and the charging volume of the refrigerant is about 1/2 to 1/3 of the charging volume of the full-fluid (flooded) chiller unit.

2.Flooded type evaporator

Water passing through inside the tube, the refrigerant completely immerses the heat exchange tube and evaporates outside the heat exchange tube after absorbing heat. There are many needle-shaped small holes on the outer surface of the heat exchange tube, and there are spiral threads on the inner surface of the tube. At the same time, the external boiling of the tube and the heat transfer in the tube are enhanced, and the heat transfer coefficient is higher than that of the dry evaporator. The disadvantage is that refrigerant charge is large, oil will accumulate in the lower part of the evaporator barrel, and reliable oil return measures must be taken.

3.Falling film type evaporator

Falling film evaporator, also known as spray evaporator. The refrigerant of this evaporator is evenly sprayed onto the heat exchange tube from the upper part of the heat exchanger. The refrigerant forms a thin liquid film on the heat exchange tube. When the refrigerant boils and evaporates, the static liquid pressure is reduced, which improves the heat exchange efficiency, and its heat transfer coefficient is higher than that of flooded evaporator. Its advantages: the refrigerant charge volume is less than that of the flooded evaporator, and it has better oil return, which can effectively avoid the risk of compressor suction with liquid.